Features:
- Input 340 ~ 550VAC, 3 phase 4 wires (dual phase operation possible)
- UL508 listed
- High efficiency up to 89%
- Short circuit, overload, over voltage & over temperature protection
- Installed on DIN rail TS35 / 7.5 or 15
- Low output ripple
- Built-in EMI filter
- Cooling by free air convection
- 100% full load burn-in
- 3 years warranty
Specifications:
| Specifications |
| Input voltage: |
340 ~ 550 VAC ; 3 phase 4 wires (dual phase operation possible) |
| Output voltage: |
Refer to table below |
| AC inrush current: |
Cold start, 50A |
| DC adjustment range: |
24 ~ 28V for 24V, 48 ~ 55V for 48V |
| Overload protection: |
105% ~ 150% output constant current limiting, auto recovery |
| Over voltage protection: |
24V: 30 ~ 36V, 48V: 59 ~ 66V |
| Setup, rise & hold up time: |
1200ms, 40ms, 20ms at 400VAC & 800ms, 40ms, 40ms at 500VAC full load |
| Withstand time: |
I/P ~ O/P: 3KV, I/P ~ FG: 1.5KV, O/P ~ FG: 0.5KV, 1 minute |
| Working temperature: |
0 ~ +50° C extended with output derating |
| Safety standard: |
UL508, UL60950-1, TUV EN60950-1 approved |
| EMC standard |
EN55022 class B, EN61000-3-2,3, ENV50204, EN61000-4-2,3,4,5,6,8,11, EN61000-6-2, EN61204-3 |
| Connection: |
I/P: 4 poles, O/P: 4 poles screw DIN terminal |
| Dimensions: |
125.5 x 125.2 x 100mm |
| Weight: |
1.3 kg |